OMRON E5CD-RX2A6M-000 E5CD-RX2D6M-000 E5CD-RX2A6M-001 E5CD-RX2D6M-001 E5CD-RX2A6M-002 E5CD-RX2D6M-002 E5CD-QX2A6M-000 E5CD-QX2D6M-000 E5CD-QX2A6M-001 E5CD-QX2D6M-001 E5CD-QX2A6M-002 E5CD-QX2D6M-002 E5
OMRON
E5CD-RX2A6M-000 E5CD-RX2D6M-000 E5CD-RX2A6M-001 E5CD-RX2D6M-001 E5CD-RX2A6M-002 E5CD-RX2D6M-002 E5CD-QX2A6M-000 E5CD-QX2D6M-000 E5CD-QX2A6M-001 E5CD-QX2D6M-001 E5CD-QX2A6M-002 E5CD-QX2D6M-002 E5CD-CX2A6M-000 E5CD-CX2D6M-000 E5CD-CX2A6M-004 E5CD-CX2D6M-004 E5CD-CX2A6M-006 E5CD-CX2D6M-006
Digital Temperature Controller (48 x 48 mm)
Specifications:
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz | |
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC | |
Sensor input | Temperature input | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output | Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Linear current | 4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000 | |
Auxiliary | Number of | 2 |
Output | SPST-NO relay outputs: 250 VAC, E5CD: 3 A (resistive load), E5CD-B: 2 A (resistive load) | |
Event | Number of | 2 |
External | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Transfer | Number of | 1 (depends on model): Transfer output type |
Output | Current output: 4 to 20 mA DC, Load: 500 Ω, Resolution: Approx. 10,000 | |
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital display, individual indicators, and bar display | |
Multi SP * | Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications. | |
Bank switching | None | |
Other functions | Adaptive control, automatic filter adjustment, water-cooling output adjustment, indication data (power ON time monitor, ambient temperature monitor, and control output ON/OFF count monitors), parameter masking, operation after power ON, manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic operations, temperature status display, simple programming, moving average of input value, and display brightness setting | |
Ambient operating temperature | -10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C with standard mounting (with no condensation or icing) | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no condensation or icing) | |
Altitude | 2,000 m max. | |
Recommended fuse | T2A, 250 VAC, time-lag, low-breaking capacity | |
Installation environment | Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1) |