Specifications:
| Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz  | |
| Operating voltage range | 85 to 110% of rated supply voltage | |
| Power consumption | 8.7 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC | |
| Sensor input | Temperature input  | |
| Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min.  | |
| Control method | 2-PID control (with auto-tuning) or ON/OFF control | |
| Control  | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,  | 
| Voltage output  | Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuit  | |
| Linear current  | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
| Auxiliary | Number of outputs | 4 | 
| Output  | SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load),  | |
| Event  | Number of inputs | 2, 4 or 6 (depends on model) | 
| External contact  | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
| Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
| Current flow: Approx. 7 mA per contact | ||
| Transfer  | Number of outputs | 1 (only on models with a transfer output) | 
| Output  | Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000  | |
| Potentiometer input | 100 Ω to 10 kΩ | |
| Setting method | Digital setting using front panel keys | |
| Indication method | 11-segment digital display and individual indicators  | |
| Bank switching | None | |
| Other functions | Manual output, heating/cooling control, loop burnout alarm, other alarm functions,  | |
| Ambient operating  | -10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C with  | |
| Ambient operating humidity | 25 to 85% | |
| Storage temperature | -25 to 65°C (with no condensation or icing) | |
| Altitude | 2,000 m max. | |
| Recommended fuse | T2A, 250 VAC, time-lag, low-breaking capacity | |
| Installation environment | Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1) | |
 
                     
                                                                         
                     