OMRON XW2R (PLCs) Connector-Terminal Block Conversion Units for PLCs
OMRON
XW2R (PLCs)
Connector-Terminal Block Conversion Units for PLCs
Specifications:
Models for Connection to OMRON PLCs
with power supply terminals
e-CON Type
Rated current | Power supply terminal block: 4 A/16 poles or 8 A/32 poles | |
Connectors/e-CON Connectors: 1 A | ||
Rated voltage | 24 VDC | |
Insuration resistance | 100 MΩ min. (at 500 VDC) | |
Dielectric strength | 500 VAC for 1 min (leakage current: 1 mA max.) | |
Ambient operating temperature | 0 to 55°C | |
Applicable | Applicable wire sizes | AWG 24 to 14 (ferrules) |
Stripped length | AWG 28-16: 8 to 10 mm |
* This is the applicable range for the power supply terminal block. For the applicable wire sizes for I/O Connectors (e-
CON), refer to "Input Device Connectors: XN2 e-CON Connectors".
without power supply terminals
Phillips screw
Rated current | 0.5 A/signal, 4 A/common | |
Rated voltage | 24 VDC | |
Insuration resistance | 100 MΩ min. (at 500 VDC) | |
Dielectric strength | 500 VAC for 1 min (leakage current: 1 mA max.) | |
Ambient operating temperature | 0 to 55°C | |
Applicable wires | Applicable wire sizes | AWG 22 to 16 (round or forked crimp terminals) |
Stripped length | 9 mm | |
Tightening | 0.5 Nm |
Slotted screw (rise up)
Rated current | 0.5 A/signal, 4 A/common | |
Rated voltage | 24 VDC | |
Insuration resistance | 100 MΩ min. (at 500 VDC) | |
Dielectric strength | 500 VAC for 1 min (leakage current: 1 mA max.) | |
Ambient operating temperature | 0 to 55°C | |
Applicable wires | Applicable wire sizes | AWG 22 to 16 (ferrules) |
Stripped length | 7 mm | |
Tightening | 0.5 to 0.6 Nm |